DR Suite Cooler Unit – Broomfield HospitalServices
key details
| Value | £40,000 |
|---|---|
| Status | complete |
| Category (CPV) | 50710000 +2 more |
| Region | East of England |
| Deadline | 23 Dec 2015 |
| Contract start | 18 Jan 2016 |
| Contract end | 8 Nov 2016 |
| SME suitable | Yes |
| OCID | ocds-b5fd17-08f6a2fe-adc9-11e6-9901-0019b9f3037b |
Award
| Supplier | Value | Date | Status |
|---|---|---|---|
| Arriba Cooltech Ltd | £94,000 | 26 May 2016 | active |
description
MEHT wishes to receive tenders for the design, manufacture, supply, delivery to site, off-loading, moving to place of work, protecting, assembly, installation, testing and commissioning of DR Suite Cooling Unit at Broomfield Hospital.
As part of a programme of works aimed at building extra resilience into the Disaster Recovery (DR) computing centre at Broomfield Hospital the DR management team has identified the need for a dedicated chilled water installation that is suitable for supplying the needs of fan coil units fitted inside the DR computer suite.
The new system will be connected into existing flow and return pipe work in such a way that cooling can be provided by either the new chiller (DUTY) or the existing Trane chiller (STANDBY).
It is required that the proposed chilled water system must also be configurable as a heat pump, in such a way that domestic hot water (DHW) heating as well as DR air conditioning functions can be simultaneously (or separately) managed from the same machine.
Although the Client is procuring the DR Suite Cooler Unit, the successful bidder will be expected to potentially enter into a novation agreement with the successful Mechanical & Electrical Contractor who will be carrying out the enabling works and acting as Main Contractor .
The bidder is to indicate within his tender if he has any reasonable objections as to why a novation may not be entered into with the successful Mechanical & Electrical Contractor.
Design Criteria
The proposed installation is required to operate on the vapour-compression refrigerating principle and as well as producing chilled water is to be fitted with a heat recovery system of the type used in heat pump installations (in which the entirety of the energy entrained in the high pressure side of the refrigerant circuit is recoverable for water heating). Refrigerating systems which are capable only of partial heat recovery from the high pressure refrigerant circuit (eg de-superheater systems) are considered to be out of scope due to their relative inefficiency when compared to full heat pump installations.
The combined chilled water and DHW plant is to be fitted with an environmentally benign and fire-safe refrigerant.
Additional information: Please refer to the Bravo e-tendering portal, link above, for ITT documentation, clarification questions and any other information relating to the ITT for DR Suite Cooler Unit – Broomfield Hospital
notice history
1 notice published against this procurement.
| Published | Type | Regime | Notice |
|---|---|---|---|
| 23 Nov 2015 | Award (award) | · | ocds-b5fd17-08f6a2fe-adc9-11e6-9901-0019b9f3037b-80490-meht-t-2015-011 |
more from MID ESSEX HOSPITAL SERVICES N H S TRUST
- MEHT/T/2017/017 Provision of Temporary works propping to Zone B Treatment Block Balconies at Broomfield Hospital - MEHT · £70,000 · 7 Sept 2017
- Provision of Electrical Remedial Works resulting from Fixed Wire Testing Services · £40,000 · 18 Nov 2016
- EPR Annexe Office Refurbishment – Broomfield Hospital · £95,000 · 18 Nov 2016
- Provision of Maintenance Services - Bed Pan Washers - Broomfield Hospital · £40,000 · 18 Nov 2016
- Provision of Emergency Lighting Maintenance Services - MEHT · £50,000 · 18 Nov 2016
- The Replacement of Retained Estates Fire Alarm System - Staff Multi Storey Car Park · £10,000 · 18 Nov 2016
- Provision of Fixed Wire Testing Services · £45,000 · 18 Nov 2016
- Ventilation System Maintenance Services · £20,000 · 18 Nov 2016
all contracts from this buyer →
similar contracts awarded
Other awarded contracts in the same category. Useful for seeing who normally wins this kind of work, and at what value.
- Provision of Security Equipment Maintenance Services · Nottingham Trent University
- NDSC-1635 Communal electrical and Fire safety Service and Maintenance Contract fro Newark & Sherwood District Council · Newark And Sherwood District Council · £1,400,000
- UKRI-5697 Electrical Maintenance Services at STFC Daresbury Laboratory · UK Research & Innovation (UKRI) · £648,000
- Provision of Access Management service: servicing, maintenance and repairs · Curo Places Limited · £1,000,000
- Zehnder Air Filters Maintenance · The Common Services Agency (more commonly known as Public Services Delivery Scotland) (PSD Scotland) · £77,580
- Maintenance of Building Management System (Hospital and SC) · NHS Golden Jubilee · £194,449
- Fire Alarm Maintenance · The Queen Elizabeth Hospital King's Lynn NHS Foundation Trust · £216,694
- PP-10164a Meridian Trust Mechanical Services · MERIDIAN TRUST · £6,000,000
source